Answers to the questions fan manufacturers, ventilation contractors and buyers ask us most about Volcano Electric EC fan motors. For full specifications, see the full range and specifications.

EC Fan Motor Technical FAQ & Sizing Guide | Volcano
volcano-electric-hse102-hse138-hse188-external-rotor-ec-motors

About Volcano Electric

Does Volcano Electric make complete fans?

No. Volcano Electric makes the EC motor and its drive; fan manufacturers build the impeller, housing and complete fan around it. If you need a finished fan, we can point you to fan makers who already use our motors.

Is Volcano Electric a manufacturer or a trading company?

A manufacturer. Motor electromagnetic design, drive hardware and control software are developed in-house, and motors and drives are assembled and tested at our own bases in Ningbo, which includes the drive PCBA line, and in Jinhua, Zhejiang, China. Magnets and windings come from specialist suppliers. Factory visits and supplier audits can be arranged.

Which certifications do Volcano EC fan motors hold?

The EC fan motor range carries CE (EMC and LVD) and is third-party certified as IE5 using IEC 60034-2-3:2024, the test method for converter-fed motors. The drives meet IEC 61800-3 category C2 and the factory runs an ISO 9001:2015 quality system. UL, ErP and BIS are supported per project: safety-relevant components are UL-recognized grade and we support the fan maker’s certification of the complete fan.

Choosing a motor

Which EC motors fit 48-inch and 61-inch exhaust fans?

A 48-inch (1220 mm) fan typically runs near 700 rpm and needs about 15 Nm: HSE-PM38H110-160N07-S4X (1.1 kW, 700 rpm, 15 Nm, IP66). A 61-inch (1530–1550 mm) fan runs near 580 rpm and needs about 25 Nm: HSE-PM38H150-160N05-S4X (1.5 kW, 580 rpm, 25 Nm); for high static pressure, HSE-PM38H220-160N07-S4X (2.2 kW, 750 rpm, 28 Nm).

Which EC fan motors run on 220 V, and what other voltages are possible?

In the catalogue, the 220 VAC models are four HSE160 ratings (0.75 kW/460 rpm, 0.85 kW/560 rpm, 1.5 kW/1500 rpm and 2.2 kW/1500 rpm, all IP66) and the external rotor HSE102 series; everything else is rated 380 VAC, and the disc drives accept up to 480 VAC. For a project, any platform can be built for 110 to 480 VAC, single- or three-phase.

Do Volcano EC motors run the same on 50 Hz and 60 Hz supplies?

Yes. The supply is rectified inside the drive, so motor speed is set by the drive and not by the grid frequency. The same model runs at the same rated speed in 50 Hz and 60 Hz markets.

Do you supply EC motors for greenhouse and inline duct fans?

Yes. External rotor HSE102, HSE138 and HSE188 motors carry the impeller directly and suit dry inline duct and circulation fans; sprayed or washed positions need the IP66 inner rotor series. In 2024, Volcano EC motors and drives replaced the AC motors in about 6,000 inline duct fan units at a greenhouse cultivation operation in the United States.

Can Volcano EC motors drive cooling tower fans?

Some, case by case; cooling towers are not our main market. Where the fan speed is inside the catalogue, such as the 960 rpm class of the HSE370 (74 Nm at 7.5 kW, 89 Nm at 9 kW), an IP66 disc motor can drive the fan directly. Large towers whose fans turn at only a few hundred rpm need more torque than the standard range; send the fan diameter, speed and absorbed power for a clear answer.

Which Volcano EC motors are IP66 and which are IP54?

Inner rotor HSE140 (0.4–1.5 kW) and HSE160 (0.75–3.7 kW) and disc-type HSE300 (4.5–9 kW) and HSE370 (7.5–22 kW) are IP66. External rotor HSE102, HSE138 and HSE188 are IP54. IP covers dust and water only; ammonia or chemical exposure needs coating, seals and fasteners specified on the order.

How do I read a Volcano EC motor model number?

The code has nine segments. In HSE-PM38H075-140N05-S4X: HSE = EC fan motor series, PM = permanent magnet synchronous, 38H = 380 VAC, 075 = 0.75 kW, 140 = frame series, N = sensorless, 05 = rated speed constant, S = natural cooling, 4X = bracket mounting. Always take the exact rated speed from the specification table.

 

Installation and operation

 

Which protections are built into the EC motor drive?

Volcano inner rotor EC fan motors protect against over-voltage, under-voltage, over-current and phase loss. The disc series HSE300 and HSE370 shut down automatically on over-temperature, over-current and over-voltage. Fault codes can be read over RS485/Modbus to see which protection acted.

Does the EC motor drive need airflow for cooling?

Yes. The integrated drive is designed for air-over cooling, so the fan’s own airflow has to pass over its heatsink. Without that airflow, at higher power the drive protects itself by derating or shutting down. Inner rotor motors above about 6 kW have an internal cooling fan.

Can Volcano EC fan motors run 24/7, and in what ambient conditions?

Yes. They are rated for S1 continuous duty, with class F insulation designed to a class B temperature rise. Standard models run from −25 °C to +60 °C, at relative humidity up to 95 % and altitudes below 1000 m. Hotter ambients need an engineered version reviewed against the actual duty.

Technology

What is the difference between an EC motor and a BLDC motor?

Both are brushless permanent magnet motors switched by electronics. “EC motor” usually means the motor and its drive form one product that connects straight to the AC mains. Many BLDC drives use six-step (trapezoidal) commutation; Volcano EC fan motors use sensorless field-oriented control with sinusoidal current, which gives lower torque ripple and quieter running on large impellers.

Is an EC motor AC or DC?

It connects to an AC supply like any AC motor. Inside, the drive rectifies the supply to a DC bus and inverts it to drive a permanent magnet synchronous motor, so no DC supply is needed on site. The “DC” sometimes seen in product names refers to that internal bus.

Still have a question?

Send it to sales@volcanoelectric.com or message us on WhatsApp at +86 136 1018 9327. Include the supply voltage, power and speed if it is about a specific fan. Contact our engineers